These NEC load calculation practice questions cover dwelling, multifamily and commercial service sizing, with the demand factors applied. A load calculation is the question most likely to appear on your exam as a multi-part problem worth several marks, so it repays the study time better than anything else. The order matters more than the arithmetic: general lighting first, then small appliance and laundry, then apply the demand factor, then add the fixed appliances, then the largest of heat or air conditioning.
⚡
Written by Kevin, a licensed
Michigan master electrician — 26 years in the trade and 17 of them as an electrical
inspector. Every answer below names the NEC section it comes from, so you learn where to
look it up rather than memorising it.
Exam tipDemand factors are where the marks are won and lost. The first block of general load gets 100%, the remainder gets 40%. Applying that to the wrong subtotal is the classic way to lose a question you actually understood.
Tap an answer to see whether you got it right, the code section it comes
from, and the reasoning worked out in full. Nothing to sign up for.
Question 1Commercial Calc
What is the maximum number of outlets for a 15A circuit?
Correct answer: B. 10
NEC 220.14 (I)
Rule — outlets on a general-purpose circuit (220.14(I))
Each general-use outlet is figured at 180 VA. Divide the circuit's capacity by 180 and round down.
Step 1 — circuit capacity
15 A × 120 V = 1,800 VA
Step 2 — divide by 180
1,800 ÷ 180 = 10
10 outlets
How to do it
Volts × amps gives the circuit's VA; each receptacle is 180 VA; round down — you can't have a partial outlet. A 15 A circuit lands exactly on 10.
Common mistakes
Rounding up.
Forgetting each outlet is 180 VA.
Using the wrong voltage.
Question 2Commercial Calc
What is the calculated load of a show window that is 13ft long?
Correct answer: A. 2,600VA
NEC 220.14(G)
Rule — show-window lighting load (220.14(G))
Show windows are figured at 200 VA per linear foot of window.
200 VA/ft × 13 ft = 2,600 VA
2,600 VA
How to do it
Just multiply the window length by 200 VA. This is the load added for the show window, on top of the general lighting.
Common mistakes
Using the 3 VA/ft² dwelling figure.
Measuring area instead of linear feet.
Question 3Dwelling Calc
What is the demand load for 4 clothes dryers in a household?
Each dryer is at least 5,000 VA. Table 220.54 gives a demand factor by the number of dryers — but 1 through 4 stay at 100% (no reduction).
Step 1 — connected load
4 dryers × 5,000 VA = 20,000 VA
Step 2 — demand factor (1–4 dryers)
100% (no reduction)
20,000 VA
How to do it
Multiply the number of dryers by 5,000 VA, then apply the Table 220.54 factor. With 4 or fewer, the factor is 100%, so nothing changes.
Common mistakes
Applying a reduction when there are 4 or fewer.
Using less than 5,000 VA per dryer.
Question 4Commercial Calc
What is the general lighting load (VA per sq ft) for a school?
Correct answer: A. 1.5 VA
NEC Table 220.42(A)
From Table 220.42(A): a school = 1.5 VA per square foot.
Answer: 1.5 VA/ft².
Question 5Multifamily
What size branch-circuit conductor and overcurrent protection are required for a 7 kVA dryer rated 240V located in the common laundry room of a multifamily dwelling?
Correct answer: D. 10AWG with 30A breaker
NEC 240.4 & 240.6
Rule — branch circuit for a fixed appliance (240.6)
Find the current (VA ÷ V), round the breaker up to the next standard size, then pick a wire that carries it.
Step 1 — current
7,000 VA ÷ 240 V = 29.2 A
Step 2 — breaker (round up, 240.6)
next standard size = 30 A
Step 3 — wire
#10 Cu carries 30 A
10 AWG with a 30 A breaker
How to do it
Watts ÷ volts gives amps; the breaker rounds up to protect the circuit; 10 AWG copper is good for 30 A (and 240.4(D) caps 10 AWG at 30 A anyway).
Common mistakes
Rounding the breaker down. Overcurrent rounds up.
Using 12 AWG — only good to 20 A.
Forgetting to convert kVA to VA first.
Question 6Commercial Calc
How many receptacle outlets are required above a show window that is 19 ft long?
Correct answer: A. 2 outlets
NEC 210.62
Rule — show-window receptacles (210.62)
At least one receptacle within 18 in. of the top of each show window — and no point along the top can be more than 6 ft from a receptacle. One outlet reaches 6 ft each way, so it covers at most 12 ft of window.
|— 3.5 ft —●———— 12 ft ————●— 3.5 ft —|
19 ft total
Each end is 3.5 ft from an outlet ✓ — and the middle is 6 ft from either one, right at the limit ✓. No point is past 6 ft, so 2 outlets does it.
2 outlets
How to do it
Divide the window length by 12 and round up — that is the fewest outlets that can keep every point within 6 ft. Then space them so no stretch between outlets is longer than 12 ft, and no end hangs more than 6 ft past an outlet.
Common mistakes
Using the old "each 12 linear ft or major fraction" wording — the current rule is the 6-ft rule.
Rounding 1.6 down to 1 — 19 ft is more than one outlet can cover.
Mixing this up with show-window lighting load (200 VA per linear foot) — that is a different question.
Question 7Commercial Calc
What is the feeder/service calculated load in KVA for 50ft of show-window light?
Correct answer: A. 10,000VA
NEC 200va x 50 220.14(G)
Rule — show-window lighting load (220.14(G))
Show-window lighting = 200 VA per linear foot of window.
200 VA/ft × 50 ft = 10,000 VA
10,000 VA (10 kVA)
How to do it
Multiply the window length by 200 VA. This load is added on top of the general lighting for the space.
Common mistakes
Using the 3 VA/ft² dwelling figure.
Measuring area instead of linear feet.
Question 8Dwelling Calc
What is the general lighting load, in VA per square foot, for a dwelling unit?
Correct answer: A. 3 VA/ft2
NEC 220.41
A dwelling unit general lighting load = 3 VA per square foot (220.41).
Answer: 3 VA/ft².
Question 9Commercial Calc
A commercial building has a 15.5 ft plug strip whose receptacles are likely to be used at the same time. What is the VA load?
Correct answer: A. 2880VA
NEC 220.14(H)(2)
Rule — multioutlet assembly load (220.14(H))
A multioutlet assembly whose receptacles are likely to be used at the same time = 180 VA per 1 ft (220.14(H)(2)).
Step 1 — round the length up to the next foot
15.5 ft → 16 ft
Step 2 — multiply by 180
16 × 180 = 2,880 VA
2,880 VA
How to do it
When the loads run together, each foot of strip counts as 180 VA — round the length up to the next whole foot, then multiply. (If the loads are unlikely to run together, it's 180 VA per 5 ft instead.)
Common mistakes
Using the 'per 5 ft' figure when the loads run together.
Not rounding the length up to the next foot.
Question 10Multifamily
Appliance demand for a 10-unit building: each unit has a 1,200 VA dishwasher, 900 VA disposal, 4,500 W water heater?
Correct answer: B. 49,500 VA
NEC 220.53 — appliance demand (75 %)
Multifamily & appliance demand (220.53 / 220.54)
Rule 220.53: where 4 or more fastened-in-place appliances are on the same feeder, apply a 75 % demand factor.
Step 1 — Per unit
1,200 + 900 + 4,500 = 6,600 VA
Step 2 — Apply 75 %
6,600 × 0.75 = 4,950 VA per unit
Step 3 — Multiply by units
4,950 × 10 = 49,500 VA
220.53 — appliance demand (75 %)
49,500 VA
How to do it
Four or more fastened-in-place appliances on a feeder get a 75 % demand factor (220.53). Multiple dryers use the Table 220.54 factor. Non-coincident loads (heat vs A/C) count only the larger of the two (220.60).
Common mistakes
Applying the 75 % factor with fewer than 4 appliances.
Adding both heat and A/C — count only the larger.
Using the wrong dryer demand percentage.
These are 10 of 803 questions
The full course carries 654 code and calculation questions plus 149 photo questions taken on real job sites — my own photographs from 17 years of electrical inspections. Every one of them is worked out like the ones above.
NEC 2023 and NEC 2026 both included, switch between them any time
Every question names the code section, so you learn to find it in the book
The whole course reads itself out loud, with the words highlighted as they are spoken
Timed 80-question practice test built like the real exam
Video lessons, drive-along audio and flash cards that bring back what you miss