Minimum branch-circuit conductor for a 30 A non-motor-generator arc welder with a 30 % duty cycle?
Rule 630.11(A): an arc-welder's supply conductor is sized from its rated primary current times a duty-cycle multiplier in Table 630.11(A).
630.11(A) — arc-welder duty cycle
Multiply the welder's rated primary current by the duty-cycle multiplier from Table 630.11(A). For a group of welders, the two largest count at 100 %, then apply 85 %, 70 %, and 60 % to the rest (630.11(B)).
- Skipping the duty-cycle multiplier.
- Reading the wrong duty-cycle factor in Table 630.11(A).
- Sizing a group of welders with all of them at 100 %.