NEC Conductor Ampacity and Derating Practice Questions
These NEC conductor ampacity and derating practice questions work from Table 310.16, with the correction factors applied step by step. Ampacity questions test two separate ideas that people run together. Derating for heat — more than three current-carrying conductors in a raceway, or a hot ambient — is done in the 90°C column. The temperature rating of the terminations under 110.14(C) is a second, separate check made afterwards. Both have to pass.
Tap an answer to see whether you got it right, the code section it comes from, and the reasoning worked out in full. Nothing to sign up for.
Six #10 THHN copper conductors are in the same raceway with an ambient temperature of 125 °F, and all lugs are rated 75 °C. What is the ampacity of the wire?
The code book works this exact problem in Annex D, Example D3(a), and it says the method in one sentence: the conductors must independently meet the requirements for (1) terminations and (2) conditions of use throughout the raceway run. Do both, then take whichever is worse.
The correction and adjustment factors are applied to the conductor's own temperature rating. The wire is THHN, so that is the 90 °C column of Table 310.16:
| #10 copper | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| ampacity | 30 A | 35 A | 40 A |
125 °F falls in the 123–131 °F row → 90 °C factor = 0.76. (The tables assume 86 °F, so a hot space derates you.)
Six current-carrying conductors is the 4–6 band → 0.80.
The lugs are 75 °C, so the terminations are judged on the 75 °C column: #10 = 35 A (110.14(C)). That is the second of the two independent checks — it is not something you derate.
Annex D, Example D3(a) sizes a feeder exactly this way: the termination is taken from the 75 °C column, the raceway run is worked from the 90 °C column with the factors applied, and the book then says “the worst case is given by the raceway conditions.” It even checks the finished conductor the same way — “195 A × 0.96 × 0.7 = 131 A.”
- Derating the 75 °C column. That gives 35 × 0.67 × 0.80 = 19 A. The 75 °C column is the termination check, not the starting point for the factors.
- Doing only one of the two checks. They are independent — sometimes the terminations win, sometimes the raceway does.
- Applying one factor, rounding, then the other. Apply both to the base at the same time.
- Counting every wire. Count current-carrying conductors only; grounds never count (310.15(F)).
What is the neutral current when phase A = 25 A and phase B = 35 A?
Multiwire branch circuit — neutral
The shared neutral carries only the difference between the two hot legs: Neutral = | Leg A − Leg B |. Balanced legs cancel to zero; the leftover unbalance is what flows.
- Adding the legs — the neutral carries the difference, not the sum.
- Forgetting that a balanced load gives 0 A on the neutral.
- Fusing or switching a shared neutral — never do it.
Single-phase 3-wire: Leg A = 40 A, Leg B = 40 A. What current is on the neutral?
On a single-phase 3-wire system, the neutral carries the difference between the two legs.
Multiwire branch circuit — balanced neutral
The shared neutral carries only the difference between the two hot legs: Neutral = | Leg A − Leg B |. Balanced legs cancel to zero; the leftover unbalance is what flows.
- Adding the legs — the neutral carries the difference, not the sum.
- Forgetting that a balanced load gives 0 A on the neutral.
- Fusing or switching a shared neutral — never do it.
Single-phase 3-wire: Leg A = 40 A, Leg B = 30 A. What current is on the neutral?
On a single-phase, 3-wire (multiwire) circuit the two hot legs share one neutral. The neutral only carries the difference between the legs — the part that isn't balanced.
Picture the two hots pushing current in opposite directions through the neutral. Equal legs cancel to zero; the leftover (the unbalance) is what flows on the neutral. Balanced 40/40 → 0 A; 40/30 → 10 A.
- Adding the legs (40 + 30 = 70). The neutral carries the difference, not the sum.
- Forgetting a balanced load gives a 0 A neutral.
- This is why you never fuse or switch a shared neutral — opening it can overload the branch.
What size THHN copper conductor is required to supply a 150 A feeder (75 °C terminals)?
The terminal rating sets which Table 310.16 column you use (110.14(C)). The terminals are rated 75 °C.
110.14(C) · Table 310.16 (75 °C column)
Use the column that matches the terminal rating (110.14(C)) — 60 °C or 75 °C for most gear, never the 90 °C column for the final pick. Go down that column to the first conductor whose ampacity meets or beats the load.
- Reading the 90 °C column for the final size — that column is only for derating math.
- Ignoring the terminal rating — the lug, not the insulation, sets the column.
- Picking a wire rated below the required amps.
What is the corrected ampacity of a #12 THHN copper conductor installed in a 50 °F ambient?
Ambient correction adjusts a conductor's ampacity when the surrounding air is hotter or cooler than the 30 °C (86 °F) base.
310.15(B)(1) / Table 310.15(B)(1)(1) — ambient temperature correction
Start at the conductor's 90 °C ampacity (Table 310.16), then multiply by the ambient-temperature correction (Table 310.15(B)(1)) and the more-than-3-conductors adjustment (Table 310.15(C)(1)). The final result still cannot exceed the terminal column's ampacity.
- Starting the math from the 75 °C ampacity instead of 90 °C.
- Applying only one factor when both ambient and fill apply.
- Counting the neutral or ground as current-carrying when it is not.
What is the adjusted ampacity of four 1 AWG THWN in one raceway?
When more than 3 current-carrying conductors share a raceway, reduce ampacity per Table 310.15(C)(1).
310.15(C)(1) — conductor fill adjustment
Start at the conductor's 90 °C ampacity (Table 310.16), then multiply by the ambient-temperature correction (Table 310.15(B)(1)) and the more-than-3-conductors adjustment (Table 310.15(C)(1)). The final result still cannot exceed the terminal column's ampacity.
- Starting the math from the 75 °C ampacity instead of 90 °C.
- Applying only one factor when both ambient and fill apply.
- Counting the neutral or ground as current-carrying when it is not.
Ampacity of four #6 THWN-2 in conduit, outdoors at 115 °F ambient?
Apply BOTH adjustments - ambient heat and conductor fill.
310.15(B)(1) & 310.15(C)(1)
Start at the conductor's 90 °C ampacity (Table 310.16), then multiply by the ambient-temperature correction (Table 310.15(B)(1)) and the more-than-3-conductors adjustment (Table 310.15(C)(1)). The final result still cannot exceed the terminal column's ampacity.
- Starting the math from the 75 °C ampacity instead of 90 °C.
- Applying only one factor when both ambient and fill apply.
- Counting the neutral or ground as current-carrying when it is not.
Six current-carrying 8 AWG THHN copper conductors (90 °C ampacity = 55 A) run through a single raceway where the ambient temperature is 40 °C. What is the adjusted ampacity?
≈ 40 A.
NEC 310.15(B) & (C)
Start at the conductor's 90 °C ampacity (Table 310.16), then multiply by the ambient-temperature correction (Table 310.15(B)(1)) and the more-than-3-conductors adjustment (Table 310.15(C)(1)). The final result still cannot exceed the terminal column's ampacity.
- Starting the math from the 75 °C ampacity instead of 90 °C.
- Applying only one factor when both ambient and fill apply.
- Counting the neutral or ground as current-carrying when it is not.
These are 10 of 803 questions
The full course carries 654 code and calculation questions plus 149 photo questions taken on real job sites — my own photographs from 17 years of electrical inspections. Every one of them is worked out like the ones above.
- NEC 2023 and NEC 2026 both included, switch between them any time
- Every question names the code section, so you learn to find it in the book
- The whole course reads itself out loud, with the words highlighted as they are spoken
- Timed 80-question practice test built like the real exam
- Video lessons, drive-along audio and flash cards that bring back what you miss
More free practice questions by topic
- NEC Grounding and Bonding Practice Questions
- NEC Wiring Methods and Raceway Practice Questions
- NEC Branch Circuit Practice Questions
- NEC Conduit Fill Practice Questions
- NEC Box Fill Practice Questions
- NEC Motor Calculation Practice Questions
- NEC Load Calculation Practice Questions
- NEC Service and Feeder Practice Questions
- NEC Hazardous Location and Special Occupancy Practice Questions
- NEC Swimming Pool and Spa Practice Questions
- NEC Transformer Calculation Practice Questions
- NEC Lighting, Appliance and HVAC Practice Questions
- NEC Solar PV, Emergency Systems and Low-Voltage Practice Questions